Heat Pumps

Inverter Compressor

Definition

An inverter compressor varies its rotational speed through a variable-frequency drive, so a heat pump modulates output continuously instead of switching on and off at full power. Typical modulation range is 25–100% of rated capacity. Modulation cuts start-stop cycling, softens starting currents, and is the main reason modern air-to-water heat pumps reach SCOP values of 3.5–5.0.

How does an inverter compressor work?

An inverter compressor is driven by a variable-frequency drive: incoming mains power is rectified to DC, then electronically reconstructed at whatever frequency the controller requests, typically spinning the compressor anywhere between about 20 and 120 Hz. A brushless DC motor and a rotary or scroll compression mechanism convert that speed directly into refrigerant mass flow — half the speed, roughly half the heat output.

The controller continuously matches compressor speed to the building's momentary heat demand, using flow temperature targets from weather-compensated control. A fixed-speed compressor knows only two states, 0% and 100%; an inverter unit lives on the whole scale between them.

Why does modulation improve efficiency?

Modulation improves efficiency because buildings almost never need full power: a central European heating season spends the large majority of its hours below half of design load. The EN 14825 standard behind SCOP reflects this by weighting part-load test points, which is where inverter machines shine.

Two mechanisms do the work:

  1. Fewer starts. Every compressor start costs energy before useful heat flows and adds mechanical wear. Long, low-speed runs replace dozens of daily starts.
  2. Oversized exchangers at part load. At 40% speed, the same evaporator and condenser serve far less refrigerant, so temperature differences shrink, condensing pressure falls and the COP rises — the compressor works across a smaller temperature lift.

As a rule of thumb, every degree of reduced flow temperature improves efficiency 2–3%, and part-load operation is what lets the controller actually hold those lower temperatures.

What changes in practice versus a fixed-speed compressor?

CriterionInverter compressorFixed-speed (on/off)
Output controlContinuous, ~25–100%Full power or off
Starting currentSoft start, low inrushInrush several times running current
Cycling at part loadRare above minimum modulationConstant
Flow temperature stabilitySteadySawtooth
Noise profileLow speed most of the timeFull speed whenever running

The soft start also matters for grid connections: no flicker, no oversized fuses, simpler approval for single-phase homes.

Does an inverter compressor remove the need for a buffer tank?

No — it weakens one argument for the buffer, not all three. When the unit can modulate below the building's minimum load, anti-cycling volume matters less. But a buffer tank also guarantees defrost energy and provides hydraulic separation for zoned circuits, and modulation does nothing for either. Zoned radiator systems and cold climates still specify a buffer; the full reasoning is in Do I need a buffer tank with a heat pump?.

Below its minimum modulation step — often 25–30% of rated output — even an inverter unit cycles. Oversizing a heat pump therefore still hurts: a 16 kW unit on a 6 kW house spends spring and autumn below its modulation floor. Correct sizing plus modulation is the combination that delivers the catalogue SCOP.

Inverter technology is standard across the European market's growth — heat pump sales rose 13% in 2025 to 2.88 million units (EHPA) — and in Solimpeks' Varm Up Series, whose EVI DC inverter units reach COP up to 4.92 at A7/W35.

Frequently asked questions

What is the difference between an inverter and an on/off heat pump?

An on/off unit always runs at full power and regulates by starting and stopping; an inverter unit varies compressor speed to match demand, typically between 25% and 100% of rated output. The inverter version cycles less, starts softly and achieves higher seasonal efficiency.

Do inverter heat pumps use less electricity?

Yes, over a season. Part-load operation with smaller temperature lifts and far fewer starts raises SCOP measurably compared with fixed-speed operation of the same nominal capacity — which is why EN 14825 rates heat pumps at part-load points rather than full power only.

Why does my inverter heat pump run almost continuously?

By design. Long, low-speed operation is its most efficient mode; a unit trickling along at 30% output is healthier and cheaper to run than one blasting at 100% and resting. Continuous running in cold weather is normal behaviour, not a fault.

Can an inverter heat pump still short-cycle?

Yes — whenever demand falls below its minimum modulation step, typically 25–30% of rated output. Oversized units and small zoned circuits cause this; correct sizing and adequate system volume, often via a buffer tank, prevent it.

Sources & further reading

About the Author

Heat pump engineering